Analisis Kinerja Struktur Gedung IGD Terpadu K.R.M.T Wongsonegoro Kota Semarang

TALITHA ZHAFIRA, Ilham Salman Ariq, Deva Eryan Sugya Mawada, Trias Widorini

Abstract


According to its geographic location, Indonesia is part of a region prone to earthquakes, as it is situated at the convergence of three tectonic plates: Eurasian, Pacific, and Indo-Australian. These plates can collide at any time, resulting in tectonic earthquakes. Due to the occurrence of earthquakes in

Indonesia, there are significant losses to buildings. Therefore, the development

of earthquake analysis on structures is necessary. Spectrum response analysis

is one of the methods used in this report, analyzing the relationship between

the structural period of buildings and the acceleration values experienced

during earthquakes.

This study focuses on the Integrated Emergency Room Building of K.R.M.T

Wongsonegoro Semarang, aiming to determine the building's safety level 

under seismic loads according to the Indonesian Earthquake Resilience Design Standard 1726;2019. The analysis includes base shear, displacement, and story drift values using the ETABS V.20 software. The analysis results indicate that the Integrated Emergency Room Building of K.R.M.T Wongsonegoro Semarang is considered safe, with a dynamic spectrum response base shear exceeding 100% of the static earthquake. The maximum displacement values obtained are 15.87 mm in the X direction and 19.08 mm in the Y direction, while the maximum story drift values are 21.64 mm in the X direction and

25.24 mm in the Y direction, ensuring the building's safety against ultimate limit performance (0.02h).


Keywords


Respon Spektrum, Base Shear, Displacement, Story Drift

References


[1] P. Simanjuntak, “EVALUASI KERUSAKAN BANGUNAN AKIBAT GEMPA DI INDONESIA,” Jurnal Rekayasa Teknik Sipil dan Lingkungan - CENTECH, vol. 1, no. 1, pp. 44–53, Apr. 2020, doi: 10.33541/cen.v1i1.1425.

[2] E. R. Hartuti, Buku Pintar Gempa . Yogyakarta: DIVA Press, 2009.

[3] K. Tjokrodimuljo, “Teknik Gempa,” Jurusan Teknik Sipil Fakultas Teknik Universitas Gadjah Mada, 1993.

[4] G. Wiarto, “Tanggap Darurat Bencana Alam Yogyakarta,” Gosyen, 2017.

[5] Ricky Januar Honarto, Banu Dwi Handono, and Ronny Pandaleke, “PERENCANAAN BANGUNAN BETON BERTULANG DENGAN SISTEM RANGKA PEMIKUL MOMEN KHUSUS DI KOTA MANADO,” Jurnal Sipil Statik , vol. 7, no. 2, pp. 201–208, Feb. 2019.

[1] A. Bambang Siswanto and M. Afif Salim, “Kriteria Dasar Perencanaan Struktur Bangunan Tahan Gempa,” Researchgate, pp. 1–15, 2018.

[2] SNI, SNI 1727-2020 Tentang Peraturan Pembebanan Minimum. 2020.

[3] SNI, SNI 1726-2019 Tentang Persyaratan Beton Struktural Untuk Bangunan Gedung. 2019.

[4] SNI, SNI 1729-2020 Tentang Spesifikasi Untuk Bangunan Gedung Baja Struktural. 2020.

[5] SNI, SNI 2847-2019 Persyaratan Beton Struktural Untuk Bangunan Gedung. 2019.

[6] Yudha Lesmana, HANDBOOK PROSEDUR ANALISA BEBAN GEMPA STRUKTUR BANGUNAN GEDUNG BERDASARKAN SNI 1726-2019, vol. 1. Makassar: Nas Media Pustaka, 2020.

[7] M. Harris, P. Pusat, T. Reduksi, R. Bencana, K. Bidang, and T. P. Sumberdaya, “KAJIAN PENERAPAN STANDAR TAHAN GEMPA PADA PEMERIKSAAN STRUKTUR GEDUNG TERBANGUN APPLICATION ASSESSMENT OF THE SEISMIC RESISTANT STANDARD ON THE EVALUATION OF EXISTING STRUCTURES,” 2019.

[8] Zhafira T, Taufiqy I, Purwanto, Mustain, and N. K. Anggraini, “Dynamic Analysis of Spectrum Response and Static Equivalent of The Semarang University College Building,” Journal of Civil Engineering, Building, and Transportation, vol. 7, no. 1, pp. 75–79, Mar. 2023.

[9] I. Iswandi and H. Fajar, “Perencanaan Lanjut Struktur Beton Bertulang,” Bandung, Penerbit ITB Bandung, 2014.

Purnomo W, “Perencanaan Struktur Gedung Bank 4 Lantai Tahan Gempa dengan Sistem Daktail Penuh di Wilayah Gempa 3,” Universitas Muhammadiyah Surakarta, 2015.