ANALISA PERANCANGAN FILTER PASIF UNTUK MEREDAM HARMONIK PADA INSTALASI BEBAN NONLINEAR

Authors

  • Hari Prasetijo

DOI:

https://doi.org/10.30595/techno.v13i1.45

Abstract

Non-linear loads increasing on a power system results in harmonic distortion (THD) increasing. Harmonic distortion increasing getting bad influences on power system components. Measurement at one of PLN's customer installations with many non-linear loads shows the amount of voltage THD 9.41% and current THD 15.05%. To reduce the harmonic distortion we can use harmonic filters. The filter designed is a single-tunned passive filter. The design of harmonic filters adapted to the dominant order occured. Filters are not only used to reduce harmonic distortion occurred but also increase power factor. From the simulation results that by installing a single-tunned passive filters on the system, voltage THD has decreased from 9.41% to 6.61% while the current THD decreased from 15.05% to 10.40%. Meanwhile, system power factor increased from 0.971 to 0.992. Keywords: Total Harmonic Distortion, Passive Filter, Nonliear Load

References

Ali, Mohammad Mahendra et all. Tanpa tahun. Analisys Of Fully Controlled 12 Pulse Converter System And Single Tuned Passive Filter Design To Reduce Harmonics. Jurnal. Surabaya: Department of Electrical Engineering , Faculty of Industrial Technology.

Cahyadi, Rifky. 2007. Upaya Penghematan Energi Listrik Dengan Cara Mereduksi Distorsi Harmonik Menggunakan Single Tunned Notch Filter. Skripsi. Depok :Program sarjana Fakultas Teknik UI.

Ferracci, Ph., 2001.Power Quality. Cahier Technique Merlin Gerin No:199.

D. William & Stevenson Jr, 1983. Analisis Sistem Tenaga Listrik edisi keempat. Erlangga : Jakarta.

Dugan, McGranaghan Beaty. 2004. Electrical Power Systems Quality. USA : McGraw - Hill.

Ferracci, Ph., 2001.Power Quality. Cahier Technique Merlin Gerin No:199

Pramnamto, Aris. 2008. Analisis Penggunaan Single Tunned Filter Sebagai Salah Satu Solusi Masalah Harmonik Pada Beban Rumah Tangga. Skripsi. Depok : Program sarjana Fakultas Teknik UI.

Rakhmawati, Renny. 2009. Filter Pasif untuk Meredam Harmonik Ke 5 dalam Sistem Tenaga Listrik. Surabaya : Jurusan Teknik Elektro Institut Teknologi Sepuluh Nopember.

Suweden, I Nengah., I Wayan Rinas. 2009. Analisa Penanggulangan THD dengan Filter Pasif Pada Sistem Kelistrikan di RSUP Sanglah. Bali : Jurusan Teknik Elektro Universitas Udayana.

Tanoto, 2005. Simulasi Filter Pasif dan Perbandingan Unjuk Kerjanya dengan Filter Aktif dan Filter Aktif Hibrid dalam Meredam Harmonisa pada Induction Furnace. Surabaya : Jurusan Teknik Elektro Universitas Kristen Petra.

Zuhal, 1990. Dasar Teknik Tenaga Listrik dan Elektronika Daya. PT Gramedia: Jakarta.

Published

2012-04-01